Product Description

The Itokii PRO Wireless Duct Temperature Sensor uses an NTC type thermistor with UL listed plenum cable to accurately measure temperatures in duct work, while maintaining a sealed environment. Can be easily installed and mounted for long term use.

PRO - Leading Enterprise Grade "Internet of Things" Solutions

PRO sensors offer 3 to 4 times the range of standard sensor platforms, extending non-line-of-sight reach to an exceptional 1,000+ feet through walls (12-14 walls typical). Using Frequency-hopping Spread Spectrum (FHSS) also allows PRO sensors to have better interference immunity from other wireless devices.

Superior power management provides PRO sensors with almost twice the battery life of Itokii’s standard wireless sensors.

  • Coin cell sensors typically last 3+ years.
  • AA and Industrial sensors typically last up to 10+ years.
PRO products employ new Encrypt-RF™ Security (256-bit Diffie Hellman key exchange and AES-128 CBC encryption for all sensor data messages), so security is maintained at all communication points from sensor to gateway, gateway to software, then back again.

 

Integrated on-board data storage allows PRO sensors to store data messages if communication to a wireless gateway is disrupted (power outage, Internet outage, or out of range). Messages that can’t be delivered will be time-stamped and stored in memory (up to the last 512 messages) until communication with the gateway is restored, at which point the messages will all be transmitted.

Over-the-air updates allow PRO products to be updated remotely if new fixes or features become available.

The standard version of this sensor is powered by two replaceable 1.5 V AA sized batteries (included with purchase). This sensor is also available with a line power option. The line powered version of this sensor has a barrel power connector allowing it to be powered by a standard 3.0 - 3.8 V power supply (Included with Line Power option upgrade). The line powered version also uses two standard 1.5 V AA batteries as backup for uninterrupted operation in the event of line power outage.

Power options must be selected at time of purchase, as the internal hardware of the sensor must be changed to support the selected power requirements.



Product Features

  • Probe temperature range of -40°C to +150°C ( -40°F to +302°F )
  • Accurate to +/- 1° C (+/- 1.8°F)
  • User Calibrated Accuracy +/- 0.25° C (±0.45°F @ 77°F)
  • UL listed plenum probe cable

What does this wireless sensor's data look like in software?

Monnit duct temperature sensor data view in software

What's in the box?

    • Wireless Sensor
    • Mounting Hardware
    • 2 x AA Batteries
  • Duct Temperature Sensor Specifications

    Probe Operating Temperature Range -40°C to +150°C ( -40°F to +302°F )
    Accuracy @ 25°C +/- 1° C (+/- 1.8°F)
    User Calibrated Accuracy +/- 0.25° C (±0.45°F @ 77°F)
    Time Constant @ 25°C 30 sec
    Cable Rating UL listed plenum cable
     

    PRO AA Specifications

    Battery Type 2 Replaceable AA 1.5 V Batteries
    Dimension 4.375 in x 2.470 in x 1.12 in
    Supply Voltage 2.0 - 3.8 V (2 x AA 1.5V Batteries or Optional Power Supply)
    Battery Life At 1 hour heartbeat setting, included AA batteries will typically last 6-8 Years. **
    Max Operating Temperature Using AA Alkaline -18°C to 55°C (0°F to 130°F)
    Max Operating Temperature Using AA Lithium -40°C to 60°C (-40°F to 140°F)
    Optimal Battery Operating Temperature +10°C to +50°C (+50°F to +122°F)
    Enclosure Material ABS
     

    PRO 900 MHz Specifications

    Operating Frequency 900 MHz Operating Frequency
    Device Range Up to 1,000 ft. non-line-of-sight, wireless device range*
    Security Diffie-Hellman Key Exchange + AES-128 CBC
    Certifications Complies with Part 15 of the FCC Rules. (FCC ID: ZTL-G2SC1)
    Complies with Industry Canada standards. (IC: 9794A-G2SC1)

     

      * Actual range may vary depending on environment.
    ** Battery life is determined by sensor reporting frequency and other variables.

     